PKF Francis Clark Torquay – Fire Alarm System Upgrade

Upgrading to a modern, addressable fire alarm system with improved reliability and future scalability

Client Request and Scope of Work

PKF Francis Clark in Torquay approached Unique Fire & Security to upgrade their existing fire alarm system to a modern, addressable platform while retaining much of the existing infrastructure where possible. The objective was to improve system reliability, enhance cause-and-effect programming, and ensure continued compliance with BS5839 Part 1:2025.

Following a detailed device download from site, we prepared a design that matched and replaced existing detectors and devices while allowing for phased upgrades where required. The works included the removal of the existing panel and installation of a new Advanced MXPro 5 control panel in the same location, alongside reconfiguration of existing loops and integration with access-controlled doors for automatic release in the event of a fire.

Products and Timeline

At the heart of the upgrade is the Advanced Electronics MXPro 5 four-loop fire control panel, complete with additional loop cards to manage the building’s device count. The system is powered by Hochiki ESP protocol intelligent devices, offering open protocol flexibility, high-integrity communication, and long-term reliability.

Where required, we installed new heat detectors, manual call points with hinged covers, integrated sounder bases and sounder beacon bases. Existing cabling and mains supplies were utilised wherever suitable, ensuring cost efficiency and reduced disruption. Five relay interfaces were incorporated to support system integrations and cause-and-effect requirements.

The upgrade was carefully planned and delivered in phases to minimise disruption to the operational office environment. Commissioning, documentation, zone charts, logbooks, and staff training were all completed as part of the final handover.

Challenges

Upgrading an existing live fire alarm system in a commercial office environment requires detailed planning and sequencing. Maintaining system integrity throughout the transition was critical, particularly where existing cabling and device locations were retained. Audibility compliance also required careful consideration, with final sound level testing undertaken post-installation to ensure full compliance with BS5839 Part 1:2025 standards.

Additionally, integration with the existing access control system required precise programming to ensure doors would release correctly under fire conditions without affecting day-to-day operation.

Results

PKF Torquay now benefits from a fully addressable, BS5839-compliant fire alarm system built on the Advanced MXPro 5 platform. The upgrade provides improved diagnostics, enhanced cause-and-effect programming capability, and greater future scalability through network expansion if required.

The building’s fire detection now covers escape routes and rooms opening onto escape routes, with additional detection installed in higher-risk areas in line with fire risk assessment recommendations. The system has a 24-hour standby battery capacity with 30 minutes of alarm operation, ensuring continued protection even during power failure.

Full certification, as-fitted drawings, O&M manuals, and compliance documentation were issued upon completion.

Why Unique

PKF Francis Clark chose Unique Fire & Security due to our experience in complex fire alarm upgrades and our strong industry accreditations, including BAFE and SSAIB. Our ability to design, install, commission, and certify the system in-house ensured a smooth transition from old to new without unnecessary disruption.

By combining technical expertise with practical planning, we delivered a future-proofed fire alarm solution that enhances safety, reliability, and long-term compliance for the Torquay office.